Insulated duct and the production floor inside the plant
Applications · Industrial Plants

Industrial Plants & Workshops: Negative Pressure and Vibration

Workshop supply and exhaust often run under negative pressure, and the wall needs a helix to stay round. Selection here is driven by pressure, not diameter alone.

ConditionsNegative pressure / high differential
Common diameters8 – 12 inch
EnvironmentVibration, dust, possibly heat
Hanger spacing1.2 m (closer spacing)
What mattersCollapse resistant, abrasion resistant, replaceable
Recommended R-valueR6.0 / R8.0

Where the problem starts

Negative pressure is the enemy of flexible duct

The wire helix does more than hold the shape — it resists negative pressure. In dust collection and exhaust systems the internal pressure sits below atmosphere; with too few wires or too little stiffness the duct is sucked flat. Once flattened the section shrinks, velocity rises, resistance spikes, and the fan runs flat out while performance keeps falling.

Three extra requirements for plant ductwork

First,Abrasion resistant: the bore wears fast under dust; second,Vibration resistant: a flexible section where it meets the fan or equipment; third,Replaceable: industrial lines are serviced often, so the duct section must come apart quickly rather than being welded shut.

Why large diameters depend on the helix

The larger the diameter, the greater the collapse moment from the same negative pressure. A 12 inch duct with the same helix density as a 6 inch one performs far worse under vacuum. For large-diameter negative-pressure work, ask about helix specification specifically, not just diameter and R-value.

Recommended spec

RoutingR-valueNotes
8 inchR6.0Standard dust-collection branches
10 – 12 inchR6.0 / R8.0Denser helix required for mains and negative-pressure sections
High-temperature sectionsR8.0Hot exhaust sections near equipment

Installation points

Reduce hanger spacing to 1.2 m

Negative pressure plus self-weight calls for closer spacing.

Flexible connection at equipment

Never butt it rigidly — leave a flexible buffer section for vibration and easy removal.

Bend radius 1.5 times outer diameter

A tight bend raises resistance and wears the jacket.

Mark airflow direction

It is easy to install the wrong way round on site, which changes how the helix takes load.

Common mistakes

Sizing by diameter alone — ignore the negative pressure and a week into operation the duct is visibly collapsed.
Using standard insulated duct as a dust-collection main — dust abrasion plus negative pressure cuts service life well short of expectation; specify an abrasion-resistant liner.
Tying hangers with wire — stress concentrates locally and wears through the jacket quickly.