Selection & sizing
Choosing the R-value and sizing the diameter decide everything downstream.
Is thicker always better? How do R4.2 and R8 differ?
It is not about thickest but about enough. R-value is thermal resistance: higher means better insulation, but the outer diameter grows with it — R4.2 around 25 mm, R6 around 38 mm, R8 around 50 mm, roughly 13 mm more per step. For a three-to-five metre branch on standard air conditioning, R4.2 is ample. Only mains over 15 m, or runs through unconditioned space, need R6. For exposed roofs, cold chain and plant rooms — humid or wide-differential settings — go straight to R8. The cost of stepping up is space and material, not wasted performance.
How do I size the diameter? I have airflow but no duct size
Work back from velocity: area A = airflow ÷ 3600 ÷ velocity, bore D = √(4A ÷ π). For example, 2000 m³/h through a main at 5 m/s gives A = 2000÷3600÷5 = 0.111 m² and D ≈ 376 mm, so the standard φ305 (12 inch) is too small — you would run two in parallel or switch to galvanised ductwork. At 800 m³/h through a branch at 4 m/s, D ≈ 266 mm and φ254 (10 inch) fits exactly. The calculator on this page works it out and returns the nearest standard diameter.
Can one grade be used for the whole run, branches and mains?
Not recommended. With R4.2 throughout, a main running twenty or thirty metres lifts terminal air temperature by 1–2 °C; the client feels the diffuser is not cold enough and no airflow adjustment makes it up. Go the other way with R8 everywhere and you pay about 30% more for nothing, and it may not fit the ceiling. Standard practice is to step it: R6/R8 on the main, back to R4.2 at terminal branches.
A 10 m roll is not long enough — can two be joined?
You can, but a joint is the weakest point in the system. Butt the two ducts over a rigid inner sleeve at least 100 mm long, press one ring of foil tape along the seam, wrap a second layer over it and finish with a protective band. Do not leave the joint in a blind corner of the ceiling — put it where there is an access panel.
Can single-layer duct be used as insulated duct? It is much cheaper
No. Single-layer ventilation duct has no glass wool, only foil or film over a wire helix. Used for cold supply, the wall sits close to the air temperature inside, drops below room dew point and condenses at once — dripping and mold in the ceiling void. It is only for exhaust, dust collection and temporary ventilation, where temperature control is not involved.
Installation
The moves most often got wrong on site — almost all rework starts here.
How tight can a bend be?
Keep the bend radius at least 1.5 times the outer diameter. Bend tighter and the foil jacket creases or splits, the wool thins at the crease, and that section is the first to condense. When space is tight, take a longer route rather than force the bend.
What counts as an acceptable joint?
Three steps: ① cut the end square and remove burrs; ② press a full ring of foil tape along the seam, at least 50 mm wide, with no bubbles or lifted edges; ③ wrap a further layer of tape or protective band over the top. A single casual wrap, or plain wrap tape instead of foil tape, and the adhesive fails within six months — moisture then follows the seam in.
What hanger spacing is right?
One every 1.5 m on horizontal runs, plus one on each side of a bend; tighten to 1.2 m for large diameters (10 inch and up) or under negative pressure. Space them wider and the duct sags under its own weight, compressing the wool in the sagging section so the R-value falls well below design — nothing shows from outside, but the insulation is compromised.
How should a wall penetration be sealed against leaks?
Make the opening at least 20 mm larger than the duct so the wall does not rub it through. After passing through, pack the gap with a non-absorbent material (rock wool strip, or polyurethane foam cut back flush — never leave a cavity) and seal both sides with mastic. A cavity is an open channel for moisture.
If space is tight, can the duct be flattened under a beam?
No. A flattened section has its insulation squeezed thinner, the R-value drops and that spot almost always condenses. The right move is to lower the ceiling level so the duct passes with a full round section; failing that, reroute or drop one diameter size.
Troubleshooting
If the problem is already there, check in this order — far more effective than blindly adding thickness.
Water dripping from the ceiling — what to check first?
Check the joints first, not the insulation thickness. The order is: ① look for a joint or elbow above the drip — nine times out of ten that is it; ② check the jacket for damage or creasing; ③ see whether that section has been flattened or the wool compressed; ④ only then ask whether the R-value is too low. Guest-room branches are usually three to five metres and R4.2 is already enough; extra thickness rarely fixes a leaking joint.
After some time in use, airflow keeps dropping
Three common causes: ① the duct has been sucked flat by negative pressure (especially in dust collection and exhaust — check helix density and hanger spacing); ② dust build-up or mold after condensation is narrowing the bore; ③ a flattened or creased elbow. First establish whether the whole run or one section is affected: the former points to the fan and total resistance, the latter means opening up that section.
Jacket splitting or lifting
Usually a fault built in during installation: a bend pulled too tight, a metal hanger clamped straight on, or non-weatherproof tape. When repairing, do not just stick a patch on — strip the old tape for 50 mm around the split and press a fresh full ring of foil tape, otherwise the new tape sits on the old and lifts again quickly.
A section in the middle has collapsed
Two possibilities: ① hangers spaced too far apart, so the duct sags under its own weight; ② insufficient helix stiffness under negative pressure, so it has been sucked in. Tell them apart visually: sagging is gradual and sits between two hangers, while collapse is local and usually shows a clear dent. Add hangers for the first; specify a denser helix for the second.
Mold and smell on the duct
It means the insulation has taken on water. Wet glass wool dries out very slowly and mold grows inside it, so the supply air carries the smell. Such duct is effectively unrepairable and has to be replaced; at the same time trace how the water got in — a leaking joint, an unsealed wall penetration, or a damaged jacket.
Materials & construction
Why two foil insulated ducts can differ twofold in price.
What materials make up the four layers?
From inside out: the core is foil-polyester laminate, sealing the bore and keeping it smooth; the insulation is glass wool, and all the thermal resistance comes from this layer; the wire helix supports it, resisting negative pressure and setting the bend radius; the jacket is foil plus polyester, blocking UV, water and site knocks. Lose any one of the four and performance drops a grade.
What does glass wool density affect?
Density affects conductivity and recovery. Too low and the wool flattens easily with poor recovery — press it once and it never comes back. Too high and the duct stiffens, bends poorly, and both weight and cost climb. At the same thickness, the one that springs back when you press it usually outlasts the one that keeps a dent.
Why must the jacket be foil rather than plastic film?
Foil blocks moisture vapour and UV. Plastic film is cheaper but far more permeable — in damp conditions vapour slowly works its way into the wool. Most film also ages badly under UV, turning brittle and splitting within a year or two outdoors or near glazing. That is why the same diameter costs so much more or less depending on jacket material.
The new duct has a smell — is that normal?
A slight material smell, like adhesive, is normal when a roll is first opened and clears with a day or two of ventilation. If it is sharp and does not go away, the adhesive or the wool binder may be substandard — use such duct with caution, especially where supply air goes directly into occupied space.
No match — try another word, or go straight toAsk us.
Did not find your answer?Describe the conditions clearly — diameter, length, ambient temperature, application — and we will answer for your actual case.