Cold-chain Warehousing & Data Halls: Cold and Humid
Humid year-round, with the outer wall below dew point — condensation is not likely, it is certain. These projects come down to one property: air-tightness.
Where the problem starts
In low-temperature work the question is not how cold, but how wet
In standard AC work, thin insulation shows up as high terminal air temperature. Low-temperature, high-humidity settings are different: whenever the outer wall falls below the surrounding dew point, moisture condenses on the surface. Slightly thin insulation or a loose joint and you see water beading the next day.
Once moisture reaches the wool, it does not come back out
Once glass wool takes on water its conductivity rises sharply, insulation drops, the wall runs colder and condensation gets worse — a positive feedback loop. Wet wool also dries out very slowly, so the loss is effectively permanent. Projects like this cannot be saved by simply going thicker; moisture must be kept out altogether.
Three details that must be got right
① Double-seal every joint; ② fill wall penetrations before sealing, leaving no air pocket; ③ fit insulation pads at hangers to avoid metal thermal bridges. Get these three wrong and even R8 is wasted.
Recommended spec
| Routing | R-value | Notes |
|---|---|---|
| Branches inside cold rooms | R8.0 | Start at 50 mm, air-tightness first |
| Plant room supply | R8.0 | All joints fully sealed in humid conditions |
| Wall and roof sections | R8.0 | Add a waterproof sleeve and sealant |
Installation points
One pressed layer of tape, then a full wrap over it.
Pack with a non-absorbent material, then sealant — never leave a cavity.
Rubber or insulation pads to break the thermal bridge.
If the return section in a plant room runs at high negative pressure, moisture is literally drawn into the insulation.