Insulated duct runs above cold rooms and plant rooms
Applications · Cold Chain & Plant Rooms

Cold-chain Warehousing & Data Halls: Cold and Humid

Humid year-round, with the outer wall below dew point — condensation is not likely, it is certain. These projects come down to one property: air-tightness.

Ambient temperature0 – 10 °C / humid plant rooms
Duct temperatureLower still, wide differential
Relative humidityOften above 80%
Run timeClose to year-round operation
What mattersNo condensation, no mold, air-tight
Recommended R-valueStart at R8.0

Where the problem starts

In low-temperature work the question is not how cold, but how wet

In standard AC work, thin insulation shows up as high terminal air temperature. Low-temperature, high-humidity settings are different: whenever the outer wall falls below the surrounding dew point, moisture condenses on the surface. Slightly thin insulation or a loose joint and you see water beading the next day.

Once moisture reaches the wool, it does not come back out

Once glass wool takes on water its conductivity rises sharply, insulation drops, the wall runs colder and condensation gets worse — a positive feedback loop. Wet wool also dries out very slowly, so the loss is effectively permanent. Projects like this cannot be saved by simply going thicker; moisture must be kept out altogether.

Three details that must be got right

① Double-seal every joint; ② fill wall penetrations before sealing, leaving no air pocket; ③ fit insulation pads at hangers to avoid metal thermal bridges. Get these three wrong and even R8 is wasted.

Recommended spec

RoutingR-valueNotes
Branches inside cold roomsR8.0Start at 50 mm, air-tightness first
Plant room supplyR8.0All joints fully sealed in humid conditions
Wall and roof sectionsR8.0Add a waterproof sleeve and sealant

Installation points

Two layers at joints

One pressed layer of tape, then a full wrap over it.

Fill wall openings before sealing

Pack with a non-absorbent material, then sealant — never leave a cavity.

Insulation pads at hangers

Rubber or insulation pads to break the thermal bridge.

Avoid running under negative pressure

If the return section in a plant room runs at high negative pressure, moisture is literally drawn into the insulation.

Common mistakes

Plain wrap tape instead of foil tape — the adhesive fails after six months and moisture follows the seam into the wool.
Spraying foam into wall openings — expanding foam absorbs water and becomes a moisture path, which is worse.
Specifying R4.2 by standard AC logic — under cold and humid conditions it will condense, and rework is extremely expensive.